The group of AGB sets was created in order to meet the needs of the most demanding users, with a lot of attention put on providing air comfort and minimizing operation costs. AGB heating sets are mainly applied in medium and high capacity facilities. They combine top quality of manufacture, modern design and high efficiency of operation. The applied constructional solutions, resulting from the analysis of market needs, result in achieving optimum heating power appropriate for the character of a particular room.
Mixing and filtration chamber consists of:
The mixing and filtration chamber is an additional equipment of AGB heating devices.
PARAMETERS |
AGB1 |
AGB2 |
Air volume |
4 000 m3/h |
3 500 m3/h |
Heater |
1-row |
2-rows |
Max. heating power for medium 90/70°C |
28 kW |
47 kW |
Difference temperature of air with medium 90/70°C |
19 K |
43 K |
Max. medium temperature |
110°C |
|
Max. medium pressure |
1,0 MPa |
|
Heater connection |
3/4" |
|
Heater capacity |
1,2 dm3 |
2,4 dm3 |
Supply to fan |
230V; 50Hz |
|
Fan motor power |
240 W |
|
Fan engine IP |
54 |
|
Max. air stream range |
20 m |
|
Noise level (in 5m) |
53 dB(A) |
|
Weight (without medium) |
26 kg |
28 kg |
Weight of mixing box |
17 kg |