Our products worldwide
Austria, Azerbaijan, Belarus, Belgium, Bulgaria, Canada, Estonia, Finland, France, Georgia, Germany, Hungary, Kazakhstan, Latvia, Lithuania, Moldova, Netherlands, Norway, Portugal, Romania, Slovakia, Spain, Sweden, Ukraine, United Kingdom, USA
Products Air handling unitsEVO-TDiscover Klimor EVO technology

EVO-T

Suspended moudlar air handling units in standard execution

Certificates
PL-EN 1886:2008
ISO 13053
ISO 9001
ISO 14001
CE

EVO-T

The combination of functional modules allows for any air treatment process, from the simplest supply and exhaust of purified air to the preparation of supply air in the range:

  • heating - water or electric heaters,
  • cooling - water or direct evaporation DX coolers,
  • primary and secondary filtration,
  • suppression,
  • heat recovery.

EVO-T components

1
2
3
4
5
6
7
8
1
Framework
  • Frameless technology
2
Casing
  • Made of 0.7 mm galvanized steel sheet with a high corrosion resistance coating bent into a U-shape
  • Wall thickness 25 mm
  • Non-flammable mineral wool filling of class A2-S1
  • Inspection covers, equipped with handles, fixed to the butterfly screw casing
  • Seal cover-casing with a flat seal
3
Base Frame
  • Frameless technology
  • Designed for suspended installation via handles
  • Handles also used as sections connectors
4
Drain pan
  • Made of stainless steel, two-way sloped, insulated with rubber mat.
  • Drainage pipe made of stainless steel pipe, led out to the side through the AHU’s wall beyond the outline.
  • Universal trap for under and overpressure in the place of operation. It is not required to elevate the frame for the pressure of 600Pa.
5
Guide vanes
  • Made of high corrosion resistant galvanized steel or stainless steel.
6
Air dumpers
  • Standard aluminium construction. The mechanism hidden in the double profile, separated from external factors.
7
Connections
  • Standard flexible connectors with connectable duct profile.
8
Additional equipment
  • “Dumbo” terminals for pressure switch hoses connection, installed on the AHU’s fixed casing
  • Lighting – low voltage led technology – option
  • Porthole – option

Functions performed

Close
Primary filter
PF
Functions and application

application

An air-conditioning and ventilation systems with standard purity requirements as preliminary filter

An air-conditioning and ventilation systems with strict purity requirements as preliminary and secondary filter

An air-conditioning and ventilation systems with standard or strict purity requirements as the final filtration stage

Catching fat particles and heavy pollutants (metal filter)

type

Metal plate filter

G2 - ISO COARSE

Plate filter:

G4 - ISO COARSE

M5 - ISOePM10-70%

Minipleat filter:

M5 - ISOePM10-70%

F7 - ISOePM2,5-60%

F9 - ISOePM1-80%

Bag filter:

M5 - ISOePM10-50%

F7 - ISOePM2,5-65%

F9 - ISOePM1-70%/80%

Construction

metal filter

Multi layer mesh covered on both sides with galvanized steel mesh mounted in 50mm thick frame

Filteration mesh made of galvanized steel

plate filter

Filter textile covered on both sides with galvanized steel mesh

Mounted in 50mm thick frame

Filter textile made of synthetic polyester filaments

minipleat filter

Mini pleat filter packages with hot melt separators

Mounted in 50/100 mm thick frame

Glass or synthetic fabric refill (100% polypropylene)

bag filter

Pockets sewn and placed on wire truss; bags lenght 300/500mm

Mounted in 25mm thick frame; eccentric crimping

Three-layer synthetic non-woven, polypropylene, using micro fibres

Parameters

 (acc. EN 13053+A1:2011 and EN 779:2012)

metal filter

Filtration grade Am: 80%

End pressure drop Δp: 120Pa

Maximum air velocity v: 4,2m/s

Maximum working temperature: 300°C

plate filter

Filtration grade Am: 82% ÷ 92%

End pressure drop: Δp: 150Pa ÷ 200Pa

Maximum air velocity v: 4,2m/s

Maximum working temperature: 90 ÷ 100°C

minipleat filter

Filtration grade Am: 95% ÷ 99%

Final pressure drop: Δp = 150Pa ÷ 200Pa

Maximum air velocity v: 4,2m/s

Maximum working temperature: 80°C

bag filter

Filtration grade Am: 95% ÷ 99%

Final pressure drop: Δp = 200Pa ÷ 300Pa

Maximum air velocity v: 3,7 ÷ 4,6m/s

Maximum working temperature: 90 ÷ 100°C 

Close
Water heating coil
WH
Functions and application

Application:

  • Heating of supply air in air conditioning and ventilation systems
  • Heating of process air in industry-grade air conditioning and ventilation systems
Construction
  • Copper tubes; aluminium fins (standard) additionaly protected by epoxy coating (EVO-P)
  • Galvanized metal sheet or stainless (EVO-P) frame
  • Mainfolds and connectors made of copper or steel respectively
  • Exchanger connection stub pipes fitted with drain and vent
  • Number of rows: 1 ÷ 6
  • Distance between fins: 1,8 / 2,0 / 2,5mm
  • Fin thickness: 0,1mm
  • Tube wall thickness: 0,37mm
  • Tube diameter: 3/8” ÷ 5/8”

 

Exchanger medium connection:

  • Connection stub pipes are on the service side of the unit.
  • Medium connection from top or bottom exchanger in order to maintain medium counter flow direction according to the air flow direction.
Parameters

(Conformance to standards: EN 308, EN 1216, EN 13053)

  • Max. medium temperature: 120°C
  • Max. medium working pressure: 1,6MPa = 16bar (tested 21 bar)
  • Max. permitted air flow speed: v = 4,6m/s
  • Max. glycol content: 50%
  • Min./max. temperature of the air: - 40/60°C
  • Protection: permissible minimum temperature of air downstream heat exchanger is monitored by freezing protection thermostat (optional)
  • Heating capacity, pressure losses, etc. available in KAD software
Close
Secondary filter
SF
Functions and application

application

An air-conditioning and ventilation systems with standard purity requirements as preliminary filter

An air-conditioning and ventilation systems with strict purity requirements as preliminary and secondary filter

An air-conditioning and ventilation systems with standard or strict purity requirements as the final filtration stage

Catching fat particles and heavy pollutants (metal filter)

type

Metal plate filter

G2 - ISO COARSE

Plate filter:

G4 - ISO COARSE

M5 - ISOePM10-70%

Minipleat filter:

M5 - ISOePM10-70%

F7 - ISOePM2,5-60%

F9 - ISOePM1-80%

Bag filter:

M5 - ISOePM10-50%

F7 - ISOePM2,5-65%

F9 - ISOePM1-70%/80%

Construction

metal filter

Multi layer mesh covered on both sides with galvanized steel mesh mounted in 50mm thick frame

Filteration mesh made of galvanized steel

plate filter

Filter textile covered on both sides with galvanized steel mesh

Mounted in 50mm thick frame

Filter textile made of synthetic polyester filaments

minipleat filter

Mini pleat filter packages with hot melt separators

Mounted in 50/100 mm thick frame

Glass or synthetic fabric refill (100% polypropylene)

bag filter

Pockets sewn and placed on wire truss; bags lenght 300/500mm

Mounted in 25mm thick frame; eccentric crimping

Three-layer synthetic non-woven, polypropylene, using micro fibres

Parameters

 (acc. EN 13053+A1:2011 and EN 779:2012)

metal filter

Filtration grade Am: 80%

End pressure drop Δp: 120Pa

Maximum air velocity v: 4,2m/s

Maximum working temperature: 300°C

plate filter

Filtration grade Am: 82% ÷ 92%

End pressure drop: Δp: 150Pa ÷ 200Pa

Maximum air velocity v: 4,2m/s

Maximum working temperature: 90 ÷ 100°C

minipleat filter

Filtration grade Am: 95% ÷ 99%

Final pressure drop: Δp = 150Pa ÷ 200Pa

Maximum air velocity v: 4,2m/s

Maximum working temperature: 80°C

bag filter

Filtration grade Am: 95% ÷ 99%

Final pressure drop: Δp = 200Pa ÷ 300Pa

Maximum air velocity v: 3,7 ÷ 4,6m/s

Maximum working temperature: 90 ÷ 100°C 

Close
Water cooling coil
WC
Functions and application
  • Cooling of supply air in air conditioning and ventilation systems
  • Cooling of process air in industry-grade air conditioning and ventilation systems
  • Dehumidyfing of process air in industry-grade air conditioning and ventilation systems
Construction
  • Copper tubes; aluminium fins (standard) additionaly protected by epoxy coating (EVO-P)
  • Galvanized metal sheet or stainless (EVO-P) frame
  • Mainfolds and connectors made of copper or steel respectively
  • Exchanger connection stub pipes fitted with drain and vent
  • Number of rows R: 2÷12
  • Distance between fins: 2,5 mm
  • Fin thickness: 0,1mm
  • Tube wall thickness: 0,37 mm
  • Tube diameter: 3/8” ÷ 5/8”
  • Droplet eliminator mounted downstream after the cooler
  • Triple sloped drain pan made of stainless steel, buil-in AHU floor
  • Drain pan equipped with polypropylene ball siphon
Parameters

(Conformance to standards: EN 308, EN 1216, EN 13053)

 

  • Min. temp. of the medium: +2°C*
  • Max. working pressure of the medium: 1,6MPa = 16bar (tested 21 bar)
  • Max. glycol content: 50%
  • Max. permitted air velocity: v = 4,0 m/s
  • Cooling capacity, pressure drop, etc. available in KAD
Close
Direct expansion cooling coil
DX
Functions and application
  • Cooling of supply air in air conditioning and ventilation systems
  • Cooling of process air in industry-grade air conditioning and ventilation systems
  • Dehumidyfing of process air in industry-grade air conditioning and ventilation systems
Construction
  • Copper tubes; aluminium fins (standard) additionaly protected by epoxy coating (EVO-P)
  • Single (100%) or double section heat exchanger
  • Galvanized metal sheet or stainless (EVO-P) frame
  • Number of cooler rows R: 2÷10
  • Distance between fins: 2,5mm
  • Fin thickness: 0,1mm
  • Tube wall thickness: 0,37mm
  • Tube diameter: 3/8” ÷ 5/8”
  • Droplet eliminator mounted downstream after the cooler
  • Triple sloped drain pan made of stainless steel, buil-in AHU floor
  • Drain pan equipped with polypropylene ball siphon

 

Exchanger medium connection

  • Connection stub pipes are on the service side of the unit.
  • Medium connection from top of the exchanger independent of air flow direction
Parameters

(Conformance to standards: EN 308, EN 1216, EN 13053)

 

  • Min. evaporating temperature of cooling medium evaporation: +3°C*
  • Max. working pressure of the medium up to 2,8MPa = 28bar (tested 32bar)
  • Max. permitted air velocity v = 4,1m/s
  • You can select an exchanger suitable for wide range of refrigerants: R134a, R407c, R410a…
  • Cooling capacity, pressure drops, etc. available in KAD selection software
Close
Electrical heater
EH
Functions and application
  • Heating of supply air in air conditioning and ventilation systems
  • Heating of process air in industry-grade air conditioning and ventilation systems
  • Preheating air in air hanglin units
Construction
  • Single or multi-stage heating components
  • Radiator heaters combined in groups
  • Casing: framework made of galvanized metal sheet
  • Connection to terminal strip
  • Overheating protection thermostat (standard)

 

Exchanger connection

  • Connecting the wires to the terminal strip of the heater are on the service side of the unit
Parameters
  • Rated voltage: 3 x 400V
  • Min. / max. rating capacity: 4 ÷ 168kW
  • Permitted min. air velocity: v = 1,5m/s
  • Max. permissible ambient temperature around heating components: 65°C
Close
Counterflow plate heat exchanger
CPR
Functions and application
  • Indirect energy recovery from exhaust air and transfer of such energy to supply air, without possibility of humidity recovery
  • Complete separation of supply air from exhaust air streams
  • Used in combined supply and exhaust units in vertical and horizonatal AHU execution
  • Passive House ready
Construction

Counterflow plate heat exchanger

  • The block is made of aluminium plates (EVO-S / EVO-H) additionaly epoxy coated (EVO-P) with separated supply and exhaust air streams flowing between them
  • 100% by-pass with installed air damper allows to “avoid” the exchanger, that is:
    - Accordingly to decrease or “to switch off” energy recovery
    - Protect the exchanger against freezing
  • Droplet separator with triple sloped drain pan built-in AHU floor
  • Drain pan equipped with polypropylene ball siphon
Parameters

(Conformance to standards: EN 308, EN 13053)

 

Counterflow plate heat exchanger

  • Max. air volume flow: 20 000m3/h
  • Efficiency: up to 92%
  • Heat-exchanger tightness for rated working parameters (250Pa) 99,5%
  • Max. air velocity: 4,5m/s
  • Max. pressure drop: 400Pa
  • Permitted pressure difference: 800Pa
  • Min. / max. working temperature: -40 ÷ 80°C
Close
Silencer
SL
Functions and application

Application

  • Installed in-to the AHU to ensure noise reduction downstream of the fan set

 

Type

  • SLC_STD (standardowy)
  • SLC_HEFF (wyższa skuteczność)
Construction
  • The block is fitted with silencing cartridges made of non-flammable mineral wool, 100 or 200mm thick
  • The surface of wool insert protected with veil
  • Mineral wool fulfillment is built by galvanized metal sheet frame (add. pliester coated EVO-H)
Parameters

Max. permitted air velocity: v = 4,5m/s

Accesories

Roof / Intake / Outtake

  • For outside unit is delivered roof and component of the intake and outtake
  • Components with water drainage to the side opposite from the viewing side can be additionally installed on AHU

 

Door Locks and Handles

  • Easy to use door locks and handles ensure safe unit maintenance

 

Inspection window

  • Inspection window enables to observe unit‘s internal operation. The diameter of plastic porthole is 200mm
  • The porthole could be use with darkwork (in option)

 

Internal lighting

  • Internal lighting enables to observe unit‘s internal operation through inspection window.
  • Economy light is used with switch outside the unit
Close
Empty section
ES
PF
Primary filter
WH
Water heating coil
SF
Secondary filter
WC
Water cooling coil
DX
Direct expansion cooling coil
EH
Electrical heater
CPR
Counterflow plate heat exchanger
SL
Silencer
ES
Empty section

Application

Offices
Shops & stores
Malls
Restaurants
Warehouses
Public facilities

Technical data

SIZE

VMIN

VOPT

VMAKS

EXTERNAL DIMENSIONS

SUPPLY OR EXHAUST UNITS

SUPPLY EXHAUST UNITS

W

H

HTOT

W1

H1

H1TOT

4100

500

1500

2000

661

355

-

1 322

-

-

1200

1000

2100

3500

961

355

-

1 932

-

-

9200

1200

2900

5200

961

475

-

1 932

-

-

Files to download

Klimor Air Designer

The web-based software offers a quick selection of products according to the specific design requirements. The software provides users with all necessary technical information.
Go to the configurator